4 Channel High-Inrush Switch Module, 4 Feeds - International Version, 230V
As part of a complete Crestron lighting system, the CLXI-4HSW4 module provides 4 independent channels of switching for high-inrush loads such as motors, HID lighting, and fluorescent ballasts, as well as incandescent, low-voltage, and neon/cold cathode lighting. Each channel is rated for 16 Amps or 1 HP, with a total module rating of 64 Amps when fed from four separate 16 Amp feeds. Air-gap relays are provided on every channel output allowing individual circuits to be serviced without disabling the entire module.
As part of a complete Crestron lighting system, the CLXI-4HSW4 module provides 4 independent channels of switching for high-inrush loads such as motors, HID lighting, and fluorescent ballasts, as well as incandescent, low-voltage, and neon/cold cathode lighting. Each channel is rated for 16 Amps or 1 HP, with a total module rating of 64 Amps when fed from four separate 16 Amp feeds. Air-gap relays are provided on every channel output allowing individual circuits to be serviced without disabling the entire module.
An override feature allows each channel to be set to a preset state during setup. In the event that Cresnet communications should be disrupted for any reason, a simple contact closure can be used to activate the override presets on a global or semi-global basis.
The CLXI-4HSW4 occupies a single module space in any CAEN or CAENIB automation enclosure. Termination of high-voltage wiring to the module is facilitated by a CLTI-4HSW4 terminal block, sold separately to enable termination of the wiring anytime prior to installing the module. CLXI modules are controlled by the PAC2 and PAC2M professional automation control systems via the Cresnet network. A 5-wire link provides bussing of the Cresnet and override signals between modules within an enclosure (interconnect jumpers included).
Load Ratings |
|
Switch Channels |
4 |
|
Per Channel |
16 Amps, 1 HP |
|
Module Total |
64 Amps |
|
Load Types |
Incandescent, Fluorescent, Low-voltage, Neon/Cold Cathode, High-Intensity Discharge (HID), Motors |
Power Requirements |
|
230 Volts AC, 50/60Hz |
Connectors on Module |
|
Module Interconnect |
(2) 5-pin 0.156 inch headers;
Cresnet/Override interconnect ports;
Connect to PAC2, PAC2M, CAEN-BLOCK, or adjacent CLXI-Series module using interconnect cable provided |
Connections via CLTI or CLTIBN Terminal Block (sold separately) |
|
LINE 1 - 4 |
(4) DIN rail terminal blocks, brown, line power inputs |
|
SW 1 - 4 |
(4) DIN rail terminal blocks, red, channel outputs |
|
N IN 1 - 4 |
(4) DIN rail terminal blocks, blue, line input neutrals |
|
N OUT 1 - 4 |
(4) DIN rail terminal blocks, blue, channel output neutrals |
Buttons |
|
SETUP |
Used for manual channel activation and TSID |
LED Indicators |
|
PWR |
(green) Indicates line power is applied to the LINE terminal |
|
NET |
(yellow) Indicates communication with the control system |
|
1 – 4 |
(red x4) Indicates state of each channel |
|
SETUP |
(red) Indicates unit is in setup/manual mode |
Environmental |
|
Temperature |
32° to 104°F (0° to 40°C) |
|
Humidity |
10% to 90% RH (non-condensing) |
|
Heat Dissipation |
42 BTU/Hr at maximum load |
Enclosure |
|
Gray metal with black heat sink, surface mount module with (2) integral mounting flanges;
Occupies 1 module space in any CAEN or CAENIB enclosure |
Dimensions |
|
Height |
7.59 in (19.27 cm) |
|
Width |
6.92 in (17.57 cm) |
|
Depth |
3.43 in (8.70 cm) |
Weight |
|
3.00 lb (1.36 kg) |