8 Channel 0-10 V Dimmer Module, Low Profile
The GLXP‑DIMFLV8‑LP is a Crestron Green Light® switching module that features 8 channels of 0-10 V dimming control. This module is part of a complete Crestron® engineered GLPS Green Light switching panel.
The GLXP‑DIMFLV8‑LP is a Crestron Green Light® switching module that features 8 channels of 0-10 V dimming control. This module is part of a complete Crestron® engineered GLPS Green Light switching panel.
For more information on Crestron Green Light commercial lighting products, please contact Crestron Sales Support Services.
Override Input
An override input is provided to allow an external contact closure to momentarily override the control system program and set each channel output to its override preset state. States can be set and saved locally from the front panel or remotely via software.
Cresnet® Communications
The GLXP‑DIMFLV8‑LP communicates with a Crestron control system using the Cresnet control network. A pair of Cresnet ports are provided on the GLXP‑DIMFLV8‑LP to allow easy daisy‑chaining of several Crestron devices.
Key Features
- 8 channels of 0‑10 V dimming control
- Compatible with lighting and motor loads
- Support for 100‑277 V applications
- 16 A load rating per channel
- Arc‑less switching
- Positive air gap at each output
- Phase‑independent channels
- Cresnet® communications
- Redundant power capability
- Local controls for testing and verification
- Local and remote override capability
- Non‑volatile power failure memory
- GLEX cabinet installation
- CEC Title 24 2013 Compliant
Load Ratings |
Dimmer Channels |
8 |
Per Channel |
16 A @ 100-277 VAC, 50/60 Hz;
0.5 HP @ 120 V, 1 HP @ 230 V, 1 HP @ 277 V |
Dim Load Types |
0‑10 V fluorescent ballast or LED driver (4‑wire);
60 mA max current sink |
Switch Load Types |
Incandescent, magnetic low‑voltage, electronic low‑voltage, neon/cold cathode, fluorescent, high‑intensity discharge (HID), motors |
Relay Lifetime |
1,000,000 on/off operations at full electronic ballast load |
Power Requirements |
Primary |
100-277 VAC, 50/60 Hz, supplied via channel 1 (L1, N1) |
Secondary (optional) |
5 W @ 24 VDC, supplied via the Cresnet® network |
Connectors |
NET |
(2) 5‑pin headers |
N1 |
(1) Terminal block;
Line input neutral;
Accepts 10‑14 AWG wire;
Torque to 4.43 lb‑in. (0.5 Nm) |
L1-L8 |
(8) Terminal blocks;
Line power inputs;
Accepts 10‑14 AWG wire;
Torque to 4.43 lb‑in. (0.5 Nm) |
SW1-SW8 |
(8) Terminal blocks;
Switch channel outputs;
Accepts 10‑14 AWG wire;
Torque to 4.43 lb‑in. (0.5 Nm) |
0-10V DIM (-) |
(1) 8‑position terminal block;
Dim channel common;
Galvanically isolated;
May be wired as Class 1 or Class 2;
Accepts 12‑28 AWG wire;
Torque to 4.43 lb‑in. (0.5 Nm) |
0-10V DIM (+) |
(1) 8‑position terminal block;
Dim channel output;
Galvanically isolated;
May be wired as Class 1 or Class 2;
Accepts 12‑28 AWG wire;
Torque to 4.43 lb‑in. (0.5 Nm) |
Controls & Indicators |
NET ID |
(2) 7‑segment green LED digits and (2) miniature push buttons, sets Cresnet ID;
Digits display output levels during local control |
SETUP |
(1) Red LED and (1) recessed miniature push button, enables setup mode and touch‑settable ID |
OVR |
(1) Red LED and (1) miniature push button, enables override mode and saves presets |
PWR |
(1) Green LED, indicates power status;
Solid illumination indicates line power is applied to N1 and L1;
Flashing indicates Cresnet power is supplied in absence of line power |
NET |
(1) Yellow LED, indicates communication with control processor |
RESET |
(1) Recessed miniature push botton, resets internal processor |
ON/OFF |
(8) Red LEDs and (8) miniature push buttons, manually activates individual channels for dimming |
Enclosure |
The GLXP-DIMFLV8-LP module mounts in a GLEX enclosure with (2) integral mounting flanges. |
Environmental |
Temperature |
32° to 104° F (0° to 40° C) |
Humidity |
10% to 90% RH (noncondensing) |
Heat Dissipation |
116 BTU/Hr |
Dimensions |
Height |
11.07 in. (282 mm) |
Width |
9.5 in. (241 mm) including mounting flanges |
Depth |
3.26 in. (82 mm) |
Compliance |
UL508, Section 41 (Endurance Test) and Section 61C (Electronic Ballasts)
UL924, Emergency Power Requirement
IEC60669‑2‑1, Section 19.102 (Contact mechanisms incorporated in electronic switches, intended for fluorescent lamp circuits or other capacitive loads)
SCCR Rating ‑ 65kA
CE
CEC Title 24 2013 Compliant |
Click
here to search product certificates.
Please select your region below to see the appropriate Advertised Pricing.